ApprovedFiled Jul 4, 2026 by Parker Stroud, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 4, 2026
- Assembly type
- DC
- Serial number
- B202479
- Size
- 3/4
- Test gauge serial
- G-9895
- Gauge calibration date
- Nov 15, 2025
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-58-01302
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.