Backflow assembly test: 3395 Mill Creek Way

Approved

Filed Jan 20, 2025 by Avery Ashby, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 20, 2025
Assembly type
DC
Serial number
W158222
Size
3/4
Test gauge serial
G-7026
Gauge calibration date
Jun 5, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-85-01207
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.