Back to the backflow review queue

Backflow assembly test: 1757 Quarry Ln

Approved

Filed Mar 9, 2024 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Mar 9, 2024
Assembly type
RP
Serial number
W949891
Size
1
Test gauge serial
G-2739
Gauge calibration date
Feb 6, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-46-01070
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1757 Quarry Ln
Owner: Alex Marsh
Parcel 017-46-01070