Backflow assembly test: 2045 Mill Creek Way

Approved

Filed Jun 25, 2024 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 25, 2024
Assembly type
PVB
Serial number
K554601
Size
3/4
Test gauge serial
G-7831
Gauge calibration date
Sep 23, 2023
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-90-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.