Back to the backflow review queue

Backflow assembly test: 7688 Pine Knoll Dr

Approved

Filed Jan 9, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jan 9, 2026
Assembly type
RP
Serial number
Z684875
Size
1
Test gauge serial
G-4634
Gauge calibration date
Oct 8, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-18-01215
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7688 Pine Knoll Dr
Owner: Shawn Danner
Parcel 017-18-01215