Back to the backflow review queue

Backflow assembly test: 4663 Pine Knoll Ct

Approved

Filed Jun 25, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 25, 2026
Assembly type
RP
Serial number
Z224269
Size
1
Test gauge serial
G-2043
Gauge calibration date
Jan 23, 2026
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-87-01069
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4663 Pine Knoll Ct
Owner: Logan Lindqvist
Parcel 017-87-01069