Backflow assembly test: Hilltop Market

Approved

Filed Feb 14, 2026 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 14, 2026
Assembly type
RP
Serial number
B274559
Size
1 1/2
Test gauge serial
G-1099
Gauge calibration date
Sep 8, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-13-01118
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4448 Mill Creek Ct
Owner: Lindqvist Holdings LLC
Parcel 017-13-01118