Backflow assembly test: 3379 Meadow Lark Ln
ApprovedFiled Jun 8, 2026 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 8, 2026
- Assembly type
- RP
- Serial number
- B362664
- Size
- 3/4
- Test gauge serial
- G-3091
- Gauge calibration date
- Dec 4, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Brandt, current on the service date
- All required fields present
- Address matches parcel 017-30-01331
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.