Backflow assembly test: 2164 Meadow Lark Ct

Approved

Filed Aug 5, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 5, 2026
Assembly type
RP
Serial number
K590515
Size
3/4
Test gauge serial
G-4438
Gauge calibration date
Feb 11, 2026
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-84-01226
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.