Backflow assembly test: Hilltop Apartments
ApprovedFiled Oct 23, 2024 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 23, 2024
- Assembly type
- DC
- Serial number
- K157361
- Size
- 4
- Test gauge serial
- G-6354
- Gauge calibration date
- Oct 14, 2023
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-74-01150
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4188 Orchard Rd
Owner: Okafor Holdings LLC
Parcel 013-74-01150