Backflow assembly test: Corner Market
ApprovedFiled Aug 24, 2025 by Morgan Vance, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 24, 2025
- Assembly type
- RP
- Serial number
- K452017
- Size
- 1
- Test gauge serial
- G-1219
- Gauge calibration date
- Jul 17, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Vance, current on the service date
- All required fields present
- Address matches parcel 013-21-01223
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9683 Laurel Ln
Owner: Brandt Holdings LLC
Parcel 013-21-01223