Approved

Filed Mar 28, 2026 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 28, 2026
Assembly type
DC
Serial number
W775884
Size
1 1/2
Test gauge serial
G-7823
Gauge calibration date
Feb 18, 2026
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-46-01245
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.