Back to the backflow review queue

Backflow assembly test: 8883 Quarry Rd

Approved

Filed Nov 11, 2024 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 11, 2024
Assembly type
RP
Serial number
Z280329
Size
3/4
Test gauge serial
G-2668
Gauge calibration date
May 27, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-20-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8883 Quarry Rd
Owner: Casey Ellery
Parcel 013-20-01296