Back to the backflow review queue

Backflow assembly test: Blue Heron Bakery

Approved

Filed Jun 28, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 28, 2025
Assembly type
DC
Serial number
W176845
Size
4
Test gauge serial
G-7270
Gauge calibration date
Mar 5, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-51-01331
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6595 Quarry Ct
Owner: Ellery Holdings LLC
Parcel 013-51-01331