Back to the backflow review queue

Backflow assembly test: 6664 Fox Run Rd

Approved

Filed Sep 19, 2025 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Sep 19, 2025
Assembly type
RP
Serial number
B338788
Size
3/4
Test gauge serial
G-7992
Gauge calibration date
Jul 19, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-14-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6664 Fox Run Rd
Owner: Blake Wexler
Parcel 013-14-01315