Backflow assembly test: 5470 Hickory Way

Approved

Filed Nov 8, 2026 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 8, 2026
Assembly type
RP
Serial number
Z951086
Size
1
Test gauge serial
G-8146
Gauge calibration date
Sep 4, 2026
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
1.2 psid
Relief valve opened at
3.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-31-01308
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5470 Hickory Way
Owner: Avery Harlow
Parcel 013-31-01308