Back to the backflow review queue

Backflow assembly test: 7211 Ridgeview Dr

Approved

Filed May 26, 2025 by Morgan Ashby, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 26, 2025
Assembly type
PVB
Serial number
Z759068
Size
3/4
Test gauge serial
G-4500
Gauge calibration date
Feb 20, 2025
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-41-01326
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7211 Ridgeview Dr
Owner: Jordan Vance
Parcel 013-41-01326