Back to the backflow review queue
Backflow assembly test: 9478 Turkey Hill Rd
ApprovedFiled Aug 7, 2025 by Casey Benton, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 7, 2025
- Assembly type
- RP
- Serial number
- K326783
- Size
- 3/4
- Test gauge serial
- G-9458
- Gauge calibration date
- Mar 1, 2025
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Benton, current on the service date
- All required fields present
- Address matches parcel 013-29-01244
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9478 Turkey Hill Rd
Owner: Shawn Kessler
Parcel 013-29-01244