Back to the backflow review queue

Backflow assembly test: 9478 Turkey Hill Rd

Approved

Filed Jul 10, 2024 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jul 10, 2024
Assembly type
RP
Serial number
K326783
Size
3/4
Test gauge serial
G-6754
Gauge calibration date
Nov 21, 2023
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-29-01244
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9478 Turkey Hill Rd
Owner: Shawn Kessler
Parcel 013-29-01244