Back to the backflow review queue

Backflow assembly test: 9478 Turkey Hill Rd

Approved

Filed Jul 3, 2023 by Morgan Ashby, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 3, 2023
Assembly type
RP
Serial number
K326783
Size
3/4
Test gauge serial
G-5608
Gauge calibration date
May 2, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-29-01244
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9478 Turkey Hill Rd
Owner: Shawn Kessler
Parcel 013-29-01244