Backflow assembly test: 3479 Turkey Hill Rd

Approved

Filed Apr 6, 2026 by Drew Ramirez, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 6, 2026
Assembly type
RP
Serial number
A335561
Size
3/4
Test gauge serial
G-9304
Gauge calibration date
Dec 17, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 013-69-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3479 Turkey Hill Rd
Owner: Hayden Hollins
Parcel 013-69-01225