Back to the backflow review queue

Backflow assembly test: Blue Heron Self Storage

Approved

Filed Sep 27, 2026 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Sep 27, 2026
Assembly type
RP
Serial number
W845441
Size
1 1/2
Test gauge serial
G-6279
Gauge calibration date
Apr 13, 2026
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-58-01324
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9789 Pine Knoll Trl
Owner: Danner Holdings LLC
Parcel 013-58-01324