Backflow assembly test: 9616 Fox Run Rd

Approved

Filed Jul 25, 2026 by Casey Benton, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jul 25, 2026
Assembly type
RP
Serial number
K793406
Size
3/4
Test gauge serial
G-9263
Gauge calibration date
Mar 14, 2026
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-96-01023
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.