Back to the backflow review queue
Backflow assembly test: Blue Heron Bakery
Needs reviewFiled Nov 29, 2026 by Parker Ashby, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 29, 2026
- Assembly type
- RP
- Serial number
- K550275
- Size
- 2
- Test gauge serial
- G-4496
- Gauge calibration date
- Apr 6, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 013-45-01080
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
5838 Turkey Hill Trl
Owner: Ramirez Holdings LLC
Parcel 013-45-01080