Backflow assembly test: Blue Heron Bakery

Approved

Filed Nov 12, 2024 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Nov 12, 2024
Assembly type
RP
Serial number
K550275
Size
2
Test gauge serial
G-7168
Gauge calibration date
Jul 19, 2023
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-45-01080
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.