Backflow assembly test: 6246 Turkey Hill Ln

Approved

Filed Oct 28, 2024 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Oct 28, 2024
Assembly type
DC
Serial number
W786920
Size
1
Test gauge serial
G-3646
Gauge calibration date
Jul 4, 2024
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-57-01336
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.