Backflow assembly test: 3699 Turkey Hill Way
ApprovedFiled Sep 13, 2025 by Drew Ramirez, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 13, 2025
- Assembly type
- RP
- Serial number
- W873499
- Size
- 3/4
- Test gauge serial
- G-6589
- Gauge calibration date
- Mar 18, 2025
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Ramirez, current on the service date
- All required fields present
- Address matches parcel 013-39-01246
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.