Backflow assembly test: 8459 Orchard Ln
Needs reviewFiled Nov 25, 2026 by Blake Marsh, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 25, 2026
- Assembly type
- RP
- Serial number
- B940024
- Size
- 3/4
- Test gauge serial
- G-8469
- Gauge calibration date
- Apr 8, 2026
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Marsh, current on the service date
- All required fields present
- Address matches parcel 013-62-01206
- Readings in range, no flags
- Result: passing. Next due date resets when approved.