Backflow assembly test: 8459 Orchard Ln
ApprovedFiled Oct 29, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 29, 2025
- Assembly type
- RP
- Serial number
- B940024
- Size
- 3/4
- Test gauge serial
- G-4503
- Gauge calibration date
- Feb 27, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-62-01206
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.