Back to the backflow review queue

Backflow assembly test: 6126 Meadow Lark Ct

Approved

Filed Oct 12, 2024 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 12, 2024
Assembly type
PVB
Serial number
K378433
Size
3/4
Test gauge serial
G-3809
Gauge calibration date
Jun 20, 2024
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-99-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6126 Meadow Lark Ct
Owner: Sam Kessler
Parcel 013-99-01147