Backflow assembly test: 3834 Sycamore Trl

Approved

Filed Sep 6, 2024 by Avery Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Sep 6, 2024
Assembly type
PVB
Serial number
W204710
Size
3/4
Test gauge serial
G-5041
Gauge calibration date
Jul 11, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 009-25-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3834 Sycamore Trl
Owner: Jordan Ellery
Parcel 009-25-01340