Backflow assembly test: 2285 Fox Run Dr
ApprovedFiled Jul 12, 2026 by Logan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 12, 2026
- Assembly type
- RP
- Serial number
- B390528
- Size
- 1
- Test gauge serial
- G-4927
- Gauge calibration date
- Apr 10, 2026
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Kessler, current on the service date
- All required fields present
- Address matches parcel 009-61-01085
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.