Back to the backflow review queue

Backflow assembly test: Hilltop Grill

Approved

Filed Mar 12, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 12, 2025
Assembly type
RP
Serial number
Z928798
Size
1
Test gauge serial
G-9465
Gauge calibration date
Jan 23, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-47-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

311 Cedar Hollow Dr
Owner: Ashby Holdings LLC
Parcel 009-47-01034