Back to the backflow review queue
Backflow assembly test: 1244 Old Church Ct
ApprovedFiled Oct 29, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 29, 2025
- Assembly type
- RP
- Serial number
- K983223
- Size
- 3/4
- Test gauge serial
- G-4011
- Gauge calibration date
- May 1, 2025
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-86-01102
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1244 Old Church Ct
Owner: Alex Benton
Parcel 009-86-01102