Backflow assembly test: Blue Heron Car Wash
ApprovedFiled Sep 13, 2026 by Avery Pruitt, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 13, 2026
- Assembly type
- RP
- Serial number
- Z838551
- Size
- 2
- Test gauge serial
- G-6318
- Gauge calibration date
- Mar 21, 2026
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 4.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Pruitt, current on the service date
- All required fields present
- Address matches parcel 009-50-01169
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.