Backflow assembly test: 9585 Turkey Hill Ln
ApprovedFiled Oct 17, 2026 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 17, 2026
- Assembly type
- DC
- Serial number
- K883990
- Size
- 3/4
- Test gauge serial
- G-4918
- Gauge calibration date
- Feb 4, 2026
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-52-01196
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.