Back to the backflow review queue

Backflow assembly test: 3247 Spring Branch Ct

Approved

Filed Aug 3, 2026 by Logan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 3, 2026
Assembly type
DC
Serial number
K901474
Size
3/4
Test gauge serial
G-7006
Gauge calibration date
Oct 15, 2025
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 009-37-01198
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3247 Spring Branch Ct
Owner: Quinn Nguyen
Parcel 009-37-01198