Back to the backflow review queue

Backflow assembly test: Riverside Market

Approved

Filed Jan 9, 2026 by Emerson Marsh, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 9, 2026
Assembly type
RP
Serial number
A915263
Size
1
Test gauge serial
G-5036
Gauge calibration date
Aug 18, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-23-01236
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3105 Orchard Ln
Owner: Whitcomb Holdings LLC
Parcel 009-23-01236