Back to the backflow review queue
Backflow assembly test: Riverside Market
ApprovedFiled Jan 15, 2025 by Blake Ellery, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 15, 2025
- Assembly type
- RP
- Serial number
- A915263
- Size
- 1
- Test gauge serial
- G-1844
- Gauge calibration date
- Nov 13, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Ellery, current on the service date
- All required fields present
- Address matches parcel 009-23-01236
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3105 Orchard Ln
Owner: Whitcomb Holdings LLC
Parcel 009-23-01236