Back to the backflow review queue

Backflow assembly test: Corner Diner

Approved

Filed Jun 10, 2026 by Reese Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 10, 2026
Assembly type
RP
Serial number
K673080
Size
1 1/2
Test gauge serial
G-3970
Gauge calibration date
Apr 24, 2026
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Benton, current on the service date
  • All required fields present
  • Address matches parcel 009-81-01163
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8331 Hickory Ln
Owner: Ramirez Holdings LLC
Parcel 009-81-01163