Backflow assembly test: Golden Dental
ApprovedFiled Sep 3, 2024 by Avery Pruitt, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 3, 2024
- Assembly type
- RP
- Serial number
- Z665906
- Size
- 2
- Test gauge serial
- G-3336
- Gauge calibration date
- Dec 16, 2023
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Pruitt, current on the service date
- All required fields present
- Address matches parcel 009-89-01133
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.