Back to the backflow review queue

Backflow assembly test: 6522 Spring Branch Ln

Approved

Filed Nov 23, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 23, 2025
Assembly type
DC
Serial number
A748185
Size
1
Test gauge serial
G-4679
Gauge calibration date
Jun 8, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-46-01200
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6522 Spring Branch Ln
Owner: Taylor Nguyen
Parcel 009-46-01200