Backflow assembly test: 181 Orchard Dr
ApprovedFiled Aug 25, 2023 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 25, 2023
- Assembly type
- PVB
- Serial number
- W765899
- Size
- 3/4
- Test gauge serial
- G-8043
- Gauge calibration date
- Nov 21, 2022
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-65-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.