Backflow assembly test: 2912 Sycamore Dr

Approved

Filed Nov 29, 2024 by Logan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 29, 2024
Assembly type
RP
Serial number
W544031
Size
3/4
Test gauge serial
G-3643
Gauge calibration date
Dec 5, 2023
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
1.7 psid
Relief valve opened at
3.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 009-32-01170
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.