Backflow assembly test: 2912 Sycamore Dr
ApprovedFiled Nov 29, 2024 by Logan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 29, 2024
- Assembly type
- RP
- Serial number
- W544031
- Size
- 3/4
- Test gauge serial
- G-3643
- Gauge calibration date
- Dec 5, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Kessler, current on the service date
- All required fields present
- Address matches parcel 009-32-01170
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.