Backflow assembly test: Riverside Brewing Co
ApprovedFiled Nov 15, 2026 by Reese Benton, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 15, 2026
- Assembly type
- RP
- Serial number
- Z205144
- Size
- 2
- Test gauge serial
- G-9293
- Gauge calibration date
- Jul 28, 2026
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Benton, current on the service date
- All required fields present
- Address matches parcel 009-98-01126
- Readings in range, no flags
- Result: passing. Next due date resets when approved.