ApprovedFiled Oct 12, 2026 by Rowan Marsh, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 12, 2026
- Assembly type
- DC
- Serial number
- B520110
- Size
- 3/4
- Test gauge serial
- G-5144
- Gauge calibration date
- Mar 27, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-17-01336
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.