Back to the backflow review queue

Backflow assembly test: 8488 Fox Run Rd

Approved

Filed Aug 9, 2024 by Emerson Marsh, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 9, 2024
Assembly type
RP
Serial number
A573420
Size
1
Test gauge serial
G-5714
Gauge calibration date
Apr 12, 2024
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-93-01243
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8488 Fox Run Rd
Owner: Jamie Wexler
Parcel 009-93-01243