Back to the backflow review queue

Backflow assembly test: 6353 Hickory Trl

Approved

Filed Jul 30, 2024 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 30, 2024
Assembly type
RP
Serial number
Z737012
Size
3/4
Test gauge serial
G-5627
Gauge calibration date
Mar 16, 2024
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-99-01251
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6353 Hickory Trl
Owner: Shawn Kessler
Parcel 001-99-01251