Back to the backflow review queue

Backflow assembly test: 3829 Old Church Way

Approved

Filed Mar 25, 2025 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 25, 2025
Assembly type
RP
Serial number
K375449
Size
3/4
Test gauge serial
G-1694
Gauge calibration date
Jan 8, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-55-01001
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3829 Old Church Way
Owner: Rowan Nguyen
Parcel 001-55-01001