Backflow assembly test: Blue Heron Diner

Approved

Filed Sep 7, 2024 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Sep 7, 2024
Assembly type
RP
Serial number
W949446
Size
1 1/2
Test gauge serial
G-3582
Gauge calibration date
May 27, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-65-01239
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

186 Laurel Way
Owner: Ashby Holdings LLC
Parcel 001-65-01239